HVLS Fans for Distribution Centres

A distribution centre is not simply a bigger warehouse. Clear heights of 32 to 40 ft, narrow aisles and near-continuous racking change both where fans can hang and what they achieve there.

The tall-building problem

Above about 30 ft, stratification gets worse and the space where a fan can actually do something gets smaller. There is more temperature gradient to recover, which is the argument for fans -- and less open volume to work in, which is the argument against putting them everywhere.

The result is usually not a grid of fans across the whole footprint. It's fans concentrated where the open volume and the people are.

Where the fans go in a DC

Very narrow aisle operations are the common misjudgement. A 24 ft fan over a VNA block moves air across the top of the racking and almost none of it reaches the operator. The honest answer for VNA is winter destratification, not summer comfort.

Zone Fan case
Inbound and outbound staging Strongest. Open floor, people on it all shift, doors cycling
Cross-aisle Good. Continuous open column the full building height
Pick module face Good, if the deck doesn't cut the airflow column
Narrow-aisle storage Weak. 5–6 ft aisles block horizontal throw
Above the racking Ineffective. Air never reaches the floor

What this does to fan count

Because so much of a DC floor is unusable for airflow, the estimator applies an obstruction factor of 0.80 for racking over 20 ft and 0.75 where mezzanines or pick modules are present. A 200,000 sq ft DC will not need 200,000 sq ft worth of fans.

The rebate is worth checking here

Distribution centres are the building type Enbridge's prescriptive incentive was written around: warehousing use, high ceilings, gas forced-air heating at roof level, thermostats at floor level. Per-unit incentives are $3,000 for fans between 12 and 18 ft, and $4,000 for 20 to 24 ft, capped by an eligible-fan-count formula based on floor area.

The conditions that most often disqualify a DC are night setbacks and radiant heating.

Size Your HVLS Fan Package In 30 Seconds

Tell us about your facility

Frequently asked questions

We run three shifts. Does that change anything?

It improves the economics. Continuous operation means the heating savings accrue around the clock rather than only during a day shift.

Our ceiling is 36 ft. Is that too tall?

No, but it changes what you're buying. Taller buildings stratify more, so the heating case gets stronger while the summer comfort case depends entirely on where the fan can hang.

Will fans disturb inventory or labels?

At full speed an HVLS fan turns at 53 RPM and produces roughly a 6 mph breeze at floor level. Light packaging in the direct column can move; most operations run below full speed.

Can one fan cover our whole staging area?

Rarely. Coverage per fan is about 8,056 sq ft at 20 ft diameter and 11,600 sq ft at 24 ft, and staging areas are usually wider than one fan's influence.